VARIO fresh-flat
- Fully electronically controlled station
- Ultrasonic flow measurement for stable hot water temperature even with the smallest tap volumes
- Pressure-independent control valves and primary volume flow measurement for simple hydraulic balancing
- Air detection in the primary circuit
- EnEV-compliant outdoor weather-compensated heating circuit control
- Modular design for step-by-step partial assembly suitable for expansion phases
- Internet connection option for visualization, analysis, optimization (see following chapter)
Areas of application
- Apartment building
The VARIO fresh-flat home station is a completely new generation in modular design. Based on a highly flexible plug-in system, individual modules can be combined hydraulically and functionally precisely for the respective application.
The heart of the system is the TWW base module with the VarCon211 electronic controller and the new, innovative „OptiStep“ control valve.
The OptiStep valve combines a high-quality stepper motor with a pressure-independent valve for particularly precise and stable
DHW heating via the plate heat exchanger using the flow-through principle (fresh water heater).
The home station supplies an apartment with hot and cold domestic hot water. In addition to the room heating supply, the station is used as required.
extended.
Thanks to the modular design, ball valve manifolds, for example, can be installed at the start of the screed and the complete station can be installed later in just a few simple steps.
be added.
Home stations can be networked via Modbus
Facilitates station configuration, media and temperature flow control, remote diagnostics
Stable heating and hot water temperatures
Ultrasonic flow measurements in the domestic hot water outlet and in the primary supply on the heating side
Precise domestic hot water preparation
Even with very low dispensing volumes thanks to the combination of OptiStep and pressure-independent valve
Functions
The MSR functions of the VarCon211 controller include:
- Domestic hot water heating
- Circulation pump control
- Weather-compensated heating circuit control
- Temperature maintenance
- Option to network and record data from several stations



Technical data
Hydraulic unit with integrated microcontroller with
- Hot water preparation using the flow-through principle, electronically controlled by stepper motor valve
- Domestic hot water priority switching via HG mixer
- Heating circuits: optional NT, HT, 3-wire, 4-wire modules
- Fitting pieces for cold water and heat meters
- Pipework in stainless steel 22 x 1 mm
Microcontroller VarCon211 with plain text display for DHW heating, circu-control, room heating
On the heating side:
- Max. Operating variables: 10 bar, 90 °C
- Flow/return temperature with tapping: 50 °C / 23 °C
- Pressure loss: 468 mbar
- Primary flow rate: 1680 l/h
On the drinking water side:
- Max. Operating pressure 10 bar
- Domestic hot water temperature: 35 - 60 °C
- DHW output: 51 kW, copper-soldered plate heat exchanger
- DHW tapping volume: 21 l/min (when heating from 10 to 45 °C)
- Pressure loss TWW: 280 mbar
- Cabinet dimensions W/H/D in mm: 500-880/880-1290/150