eXergie storage system basic - kit
for difficult installation conditions - DO-IT-YOURSELF
- Delivery in one piece
- Cutting open the container at the perforated points
- Contribution to the location
- Reconstruction, welding and testing by craftsmen
- Insulation standard 100mm
Areas of application
- Detached house
- Apartment building
- Industry
The desired storage geometry does not fit through the door or staircase? Costs need to be taken into account?
Our solution for professionals - perforated storage tank kit.
Intelligent networking
Conserving resources
Future-proof
Application
Delivery status:
Middle ring offset by 120 mm, so no cross seam necessary during production.
Construction site assembly and installation:
Buffer cylinder kit for use in rooms with a minimum height of 2000 mm.
Smallest insertion opening: 700 x 1800 mm
What is required for assembly:
- Sufficiently large openings and passages for inserting the individual parts
- Separating tool for completely dividing the buffer tank
- Lifting gear, transport trolleys, etc., if necessary.
- Sufficient space for temporary storage
- Clean, dry place (room temperature at least 10°C) Space requirement: at least approx. 1 meter on two sides
- Fused power connection 230V/400V at least 2 x 16A or 1 x 32 A near the construction site
- Sufficiently good lighting of the assembly area
- Certified welders according to DIN 9606 for steel
- Construction site tools - recommendation: welding equipment, ladders, winch, spirit level, straightedge, lighting, chain hoist, toolbox
- Water pressure test 1.5 x operating pressure